Exposure Assessment of Infectious Virus Particles in a Classroom Setting Using Computational Fluid Dynamics Model

Authors

  • Eliot Lee Hawthorne Christian Academy
  • Isaac Lee

DOI:

https://doi.org/10.47611/jsr.v12i4.2216

Keywords:

infectious virus partivles, computational fluid dynamics, negative pressure system, respirable particles, school classroom setting

Abstract

Indoor air quality in classrooms directly affects comfort, focus, and academic performance. This research leveraged Computational Fluid Dynamics (CFD) to analyze the dispersion of infectious virus particles in classrooms. While Negative Pressure Systems (NPS) are often used at medical centers to inhibit virus particles’ dispersion, those are seldom applied in educational settings. The study aimed to pinpoint optimal ventilation and heating/AC flow rates to prevent virus particle spread. Results showed that prioritizing a higher flow rate at the ventilation unit over the heating/AC unit creates a negative pressure differential, decreasing virus dispersion by up to 93%. To establish negative pressure, the minimum flow rate ratio of ventilation to heating/AC should be 1.0. But for maximal virus particle reduction, a ratio of 2.8 is optimal. This research underscores CFD's value in understanding NPS dynamics and simulating virus behavior in classrooms. The findings suggest that NPS implementation in schools could significantly curb virus particle spread.

Downloads

Download data is not yet available.

Metrics

Metrics Loading ...

References or Bibliography

Autodesk Computational Fluid Dynamics (CFD) ® User Guide (2023). https://help.autodesk.com/view/SCDSE/2023/ENU/?guid=GUID-B3B67A19-0CF3-424B-9C77-F474453C7C1B, accessed as of Aug. 20, 2023

Centers for Disease Control and Prevention (2013). Airborne Infections Isolation (AII) Room. CDC.gov,

www.cdc.gov/tb/webcourses/course/chapter7/7_infection_control_7_infection_control_program_airborne_infection_isolation_aii_room.html. Accessed as of Aug. 20, 2023

Centers for Disease Control and Prevention (2023). Interim Infection Prevention and Control Recommendations for Healthcare Personnel during the Coronavirus Disease 2019 (infectious virus) Pandemic. CDC.gov, www.cdc.gov/coronavirus/2019-ncov/hcp/infection-control-recommendations.html. Accessed as of Aug. 20, 2023

Centers for Disease Control and Prevention (2020). Operating Schools during infectious virus: CDC's Considerations. CDC.gov, www.cdc.gov/coronavirus/2019-ncov/community/schools-childcare/schools.html. Accessed as of Aug. 20, 2023

Environmental Protection Agency (2023). Particulate Matter (PM) Basics. EPA.gov,

www.epa.gov/pm-pollution/particulate-matter-pm-basics. Accessed as of Aug. 20, 2023

Fernstrom, A. (2013). Aerobiology and Its Role in the Transmission of Infectious Diseases. Journal of Pathogens, 2013:493960. doi:10.1155/2013/493960.

Ferrari, S., Blázquez, T., Cardelli, R., Puglisi, G., Suárez, R., & Mazzarella, L. (2022). Ventilation strategies to reduce airborne transmission of viruses in classrooms: A systematic review of scientific literature. Build Environ. 2022 Aug 15;222:109366. doi: 10.1016/j.buildenv.2022.109366.

Kim, S. (2021). Effectiveness of Negative Pressure Isolation Stretcher and Rooms for SARS-CoV-2 Nosocomial Infection Control and Maintenance of South Korean Emergency Department Capacity. The American Journal for Emergency Medicine, 45 (483-489). https://doi.org/10.1016/j.ajem.2020.09.081.

Na, H., Choi, H., Kim, H., Park, D., Lee, J., & Kim, T. (2023). Optimizing indoor air quality and noise levels in old school classrooms with air purifiers and HRV: A CONTAM simulation study. Journal of Building Engineering, 73. https://doi.org/10.1016/j.jobe.2023.106645

Sadrizadeh, S., Yao, R., Yuan, F., Awbi, H., Bahnfleth, W., Bi, Y., Cao, G., Croitoru, C., de Dear, R., Haghighat, F., Kumar, P., Malayeri, M., Nasiri, F., Ruud, M., Sadeghian, P., Wargocki, P., Xiong, J., Yu, W., & Li, B. (2022). Indoor air quality and health in schools: A critical review for developing the roadmap for the future school environment. Journal of Building Engineering, 57. https://doi.org/10.1016/j.jobe.2022.104908.

Published

11-30-2023

How to Cite

Lee, E., & Lee, I. (2023). Exposure Assessment of Infectious Virus Particles in a Classroom Setting Using Computational Fluid Dynamics Model. Journal of Student Research, 12(4). https://doi.org/10.47611/jsr.v12i4.2216